Standard 7.8
Standard statement
The Agency has access to a backup power source, or other alternate means of communications, in order to maintain operation of radios and telephones during a power failure. The backup power source or alternate means of communication has security measures to prevent unauthorized access or tampering. At least quarterly documented testing of the back-up system is required.
Each bullet must stand alone when establishing compliance, with proofs identified for every lettered requirement.
- a.Discussion:
- b.If the back-up power source is a generator, then the generator “has security measures to prevent unauthorized access or tampering.” This can be achieved by any number of means including fencing with locked or secured gates; locking all access panels and fuel fill caps in some manner to prevent or clearly show evidence of tampering should it occur; or having the generator inside a secured area, such as a fenced back area of a station with secure access and locked panels and fuel fill cap. Having the area monitored by video cameras would provide additional security.
- c.If the back-up system is a battery operated portable radio or other battery back-up system, the system must also be protected from unauthorized access or tampering. Battery backup systems must provide a minimum of 2 hours of continuous use to allow the agency administration to make alternate arrangements for continuous operations.
- d.The department needs to have documentation that shows the generator or UPS system has been tested regularly as per departmental policy. This can be some form of log or receipt from a company which tests the system at least quarterly.